2.2.2
Connection of monitoring devices
As required by IACS UR M10 the OMD device can be connected to Schaller's remote
monitoring device Remote Indicator II to monitor the oil mist concentration and the
OMD status from a safe location.
The connection to the monitoring device is accomplished via a RS485 two-wire bus.
In case of a Remote Indicator II the connection is only a two point link. The bus
system at the OMD device must be terminated by the resistor. It is integrated in
the terminator (see
), which is supplied with the monitoring device.
The used communication cable must be twisted pair and shielded. We recommend
LAPPKABEL UNITRONIC-FD CP (TP) plus UL-CSA, AWG20. The total bus length is
limited to 400 m. The VISATRON® device cable entry (see
) at the
VISATRON® device is designed for cable diameter between 7.5 and 10.0 mm.
Figure 20:
Cable entry and bus-terminator on the bottom side of the VISATRON®
device
The connection between the OMD device and the monitoring device for standard
applications is shown in the following wiring diagram (
WARNING! The shield must be connected directly at the
cable grommet.