26
DANGER!
In some applications, it is not safe to clear a fault automatically. Automatic fault restart
function should not be enabled in such applications.
No.
Parameter Name
Setting Range
Default
L5-01
Number of Auto Reset Attempts
0 to 1
0
o: Operator Related Settings
o3: Copy Function
These parameters are used to adjust and control the Copy function of the digital operator. The Copy
function, stores parameter settings into the memory of the digital operator to facilitate the transfer of
those stored settings to other drivers with the same model, capacity, and control mode setting.
■
o3-01 Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
Parameter Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
Setting 0: Copy Select (no function)
Setting 1: INV
→
OP READ
Copies all parameters from the drive to the digital operator.
Note:
The copy protection for the digital operator is enabled by default. Set o3-02 to 1 to unlock copy
protection.
Setting 2: OP
→
INV WRITE
Copies all parameters from the digital operator to the drive.
Setting 3: OP
↔
INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if
they match.
■
o3-02 Copy Allowed Selection
It allows and restricts the use of the Copy function.
No.
Parameter Name
Setting Range
Default
o3-02
Copy Allowed Selection
0 or 1
0
Setting 0: Disabled
Setting 1: Enabled
S: Elevator Parameters
This section describes various functions needed to operate an elevator application: braking sequence
and slip compensation.
S1: Brake Sequence
■
S1-00: Zero Speed Level at Start
Determines the frequency to begin acceleration after DC Injection.
No.
Parameter Name
Setting Range
Default
S1-00
Zero Speed Level at Start
0.00 to 10.00
0.2
■
S1-01: Zero Speed Level at Stop
Determines the frequency to begin applying DC Injection when the drive is ramping to stop.
No.
Parameter Name
Setting Range
Default
S1-01
Zero Speed Level at Stop
0.00 to 10.00
0.2