SBS MicroSMART Battery Charger Technical Handbook
Air pump
The remote output is activated when the Air-pump flag is set in the
charging curve. Please see the charging curve definition for details
when and how this flag is set.
When the
Air pump
is activated, air pump pressure monitoring is
also activated. If the pressure is to low (<3 kPa) or high (>12 kPa) an
alarm is trigged.
The following settings can be made from sub menu:
•
Pump on(min)
•
Pump cycle(min)
5.5.7.3.
Extra inputs
The
Extra inputs
menu contains the additional inputs available when using the multi I/O board.
If a board is connected available inputs are shown in the menu as:
IN1A
The input is activated when IN1 on the multi I/O board is connected
to battery minus.
Available selections for this input are according to
Remote input
.
IN2A
If jumpers on J8 are mounted as
then the
input is activated when IN2 on the multi I/O board is connected to
battery minus.
If jumpers on J8 are mounted as
then the
input is activated when IN2 on the multi I/O board is supplied with
min 3 mA current.
WARNING!
The current must not exceed 10
mA/15 V.
Available selections for this input are according to
Remote input
IN3A
If jumpers on J8 are mounted as
then the
input is activated when IN3 on the multi I/O board is connected to
battery minus.
If jumpers on J8 are mounted as
then the
input is activated when IN3 on the multi I/O board is supplied with
3 mA current.
WARNING!
The current must not exceed 10 mA/15
V.
Available selections for this input are according to
Remote input
IN4A
The input is activated when IN4 on the multi I/O board is
connected to battery minus.
Available selections for this input are according to
Remote input
5.5.7.4.
Extra outputs
The
Extra outputs
menu contains the additional outputs available when using the multi I/O
board. If a board is connected available inputs are shown in the menu as: