SBS MicroSMART Battery Charger Technical Handbook
5.3.2.1.
Alarms
In the alarms view any alarm that occurs during the ongoing charge is shown. If no alarms
present, this menu cannot be entered.
5.3.2.2.
Charging param
In the
Charging param
menu the charging parameters being used in the ongoing charge can
be seen, these parameters are stored when a battery is connected. If parameters in the
Service
Charging param
menu are altered during an ongoing charge those parameters will be used
after the battery is disconnected and reconnected again.
Source
The source of the charging parameters. The possible values are:
•
User def
.
•
BMU
.
•
Dual
.
•
Multi.
A detailed description of
Source
is found in
Service Charging param
section.
B-ID
Battery monitoring unit id, if present.
Curve
Name of the charging curve being used.
Capacity
Battery capacity being used (in ampere hours).
Cells
Number of cells being used.
Cable Ri
Battery cable resistance being used.
Base load
Base load being present in the charging circuit during charging.
5.3.2.3.
Momentary data
Momentary data shows actual measured values in the charger.
Phase
Current charging phase.
P (W)
Power delivered from the charger. This indicates the total power
and is only equal to
U(VPC)*I(A)
if
Cable Ri
and
Base load
is set to
zero.