Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-21
Function
Description
Temperature measurement
The integrated temperature sensor can be used to meas
-
ure the room temperature.
To activate parameterisation, the
,
,
and
keys should be pressed together. The temperature
symbol on the display will then flash and the current set
-
ting will be displayed.
OFF: Temperature measurement disabledIf the room con
-
troller uses the temperature measurement from the room
control unit, the current room temperature in the room
controller will become invalid (99.9°C). See room control
-
ler configuration.
ON: Temperature measurement is enabled. The room
temperature will be transmitted after any 0.2°C change or
after 15 minutes without any change.
ON with temperature display: Temperature measurement
is enabled and the current room temperature will be per
-
manently shown on the display.
Factory setting: OFF
Retain settings
The settings for the fan and the set-point displacement
may be permanently applicable or only valid for the current
configuration step.
Retain settings
Press
and
keys together for at least 5 seconds. The
temperature and fan symbols will flash and status ON will
be displayed.Settings are only valid for the current con
-
figuration step.
Press
and
keys together for at least 5 seconds. The
temperature and fan symbols will flash and status OFF will
be displayed.
Factory setting: ON
Blind rotation
The rotation function can be used to control venetian
blinds. When active, the rotation command is issued with
the
key.
Deactivate rotation functionPress the
and
keys
together. On the display, the rotation symbol will flash and
the status text OFF will be displayed.
Activate rotation function
Press the
and
keys together. On the display, the
rotation symbol will flash and the status text ON will be
displayed.
Factory setting: OFF