Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-14
Function
Description
Presence
The two function keys
and
can be used to
change the operating mode manually to Comfort or Stand
-
by/unused. The operating mode is shown on the display
for approx. 20 seconds. The person symbol outside the lit
-
tle house indicates non-use; inside the house, it indicates
presence. After this, the display returns to the default view.
Fan control
The fan setting is activated with the function key
.
The display shows a fan symbol. The
and
keys
can now be used to set the fan speed manually.
Version SV1.5
SV6.1 (as from april 2008)
Fan stopped
OFF
Fan step 1
ON1
Fan step 2
ON2
Fan step 3
ON3
Fan automatic
A
Auto
The PCD7.L60x room controllers can only switch the fan
to the desired step if this is allowed by the fan operating
window. See description of the associated configuration
parameters.
Light control
The function key
is used to select the menu for light
-
ing control and to select the desired light group. Pressing
the same key several times selects all (ALL) or only one
light group (1...4), which can then be switched on and off
manually with the
and
keys.
See description of the associated configuration param
-
eters.
Blind control
The function key
is used to select the menu for blind
control and to select the desired blind group. Pressing the
same key several times selects all (ALL) or only one blind
group (1...4), which can then be raised and lowered manu
-
ally with the
and
keys.
See description of the associated configuration param
-
eters.
Commissioning / configuration
The room control unit has its own configuration parameters, which can be queried
and changed with a certain key combination.
To activate the parameter mode, the defined combination of keys should be pressed
together for at least 1 second. The display will then switch to parameter mode. The
and
keys can be used to change the parameter. If no key has been pressed