Digital room controller units
4-2
Cables
PCD7.L672
Preconfigured cable to connect extension modules to each other and to a room
controller.
PCD7.L672-xx
4
3
1
RJ9
2
1
2
4
3
0.3 m, 10 m, 50 m
RJ11
Extension module
PCD7.L62x, PCD7.L650
Room controller RC-Bus
PCD7.L60x, PCD7.L61x
Length
0.3 m, 10 m, 50 m
Plug connector
RJ-11 / RJ-9
To fit:
Room controllers:
PCD7.L60x, PCD7.L61x
Extension modules:
PCD7.L62x and PCD7.L650
PCD7.L673
Cable set to make up a PCD7.L670 and a PCD7.L672 cable.
Includes:
Cable
length 11 m
Plug connector
1
×
RJ-11
3×
RJ-9
Note:
A crimping tool is needed to press in the RJ plug connector; this can be obtained from
retailers.
4
3
1
RJ9
2
1
2
4
3
RJ11
4
3
1
RJ9
2
1
2
4
3
RJ9
First extension module
PCD7.L62x, PCD7.L650
Room controller RC-Bus
PCD7.L60x, PCD7.L61x
Last extension module
PCD7.L62x, PCD7.L650
Digital room control unit
PCD7.L64x, PCD7.L66x
Cable set PCD7.L673
Instructions:
1.
Cable cut to size and strip the outer sheath on both sides about 5 mm.
2.
The one cable end with even insulated wires in the connector plug and an
RJ-pressed with the forceps.
3.
Proceed with the other end of the cable as well, but twisted the cable end by 180°
in the connector insert and crimp.