Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Programming
Programming with series xx7
3
3-8
The following table describes the temporarily variables of
the diagnostic interrupt OB 82:
Variable
Data type
Description
OB82_EV_Class
byte
Event class and identifier:
• B#16#39: incoming event
OB82_FLT_ID
byte
Fault identification code (B#16#42)
OB82_PRIORITY
byte
Priority class (priority of OB execution)
OB82_OB_Numbr
byte
OB No. (82)
OB82_RESERVED_1
byte
Reserved
OB82_IO_FLAG
byte
Input module: B#16#54
OB82_MDL_ADDR
word
Logical base address of module with fault.
OB82_MDL_DEFECT
bool
not relevant (0)
OB82_INT_FAULT
bool
not relevant (0)
OB82_EXT_FAULT
bool
not relevant (0)
OB82_PNT_INFO
bool
not relevant (0)
OB82_EXT_VOLTAGE
bool
not relevant (0)
OB82_FLD_CONNCTR
bool
not relevant (0)
OB82_NO_CONFIG
bool
not relevant (0)
OB82_CONFIG_ERR
bool
No configuration: Shows that the checksum of
the actual configuration is wrong.
OB82_MDL_TYPE
byte
not relevant (0)
OB82_SUB_MDL_ERR
bool
User module is wrong or missing
OB82_COMM_FAULT
bool
Communication fault
OB82_MDL_STOP
bool
not relevant (0)
OB82_WTCH_DOG_FLT
bool
not relevant (0)
OB82_INT_PS_FLT
bool
not relevant (0)
OB82_PRIM_BATT_FLT
bool
not relevant (0)
OB82_BCKUP_BATT_FLT
bool
not relevant (0)
OB82_RESERVED_2
bool
not relevant (0)
OB82_RACK_FLT
bool
not relevant (0)
OB82_PROC_FLT
bool
not relevant (0)
OB82_EPROM_FLT
bool
not relevant (0)
OB82_RAM_FLT
bool
not relevant (0)
OB82_ADU_FLT
bool
No compensation: Shows that the checksum of
the actual compensation data is wrong.
OB82_FUSE_FLT
bool
not relevant (0)
OB82_HW_INTR_FLT
bool
not relevant (0)
OB82_RESERVED_3
bool
not relevant (0)
OB82_DATE_TIME
date and time Date and time the OB started.
If you do not program OB82, the CPU changes to stop mode when a diagnostic inter
-
rupt is triggered.
Interface STEP
®
7
⇔
PCDx.W745
The following address information are meant as offsets in each input or output win
-
dow. E.g. if the input range definition starts at
PEB 300
(German Mnemonics) an ac
-
cess to offset 1 means
L PEx 301
where x can be B or W. All further absolute access
within the xx7 programming relate to the above definition.