Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Programming
Programming with PCD Classic
3
3-5
The temperature unit has no influence to voltage / ohm measurement ranges.
FB Exec
Parameter structure:
FB Exec
Parameter
Type
Description
K 1…16
[K] input
Module Number accord. to file D2W745_B.mba
ValueCH0
[R] output Measured value CH0
OverR_0
[F] output
OverRange indicator for input 0
UnderR_0
[F] output
UnderRange indicator for input 0
SnsFail_0
[F] output Sensor fail indicator for input 0
T CH1
[R] output Temperature value input 1 in 1/10 [Unit]
OverR_1
[F] output
OverRange indicator for input 1
UnderR_1
[F] output
UnderRange indicator for input 1
SnsFail_1
[F] output Sensor fail indicator for input 1
T CH2
[R] output Temperature value input 2 in 1/10 [Unit]
OverR_2
[F] output
OverRange indicator for input 2
UnderR_2
[F] output
UnderRange indicator for input 2
SnsFail_2
[F] output Sensor fail indicator for input 2
T CH3
[R] output Temperature value input 3 in 1/10 [Unit]
OverR_3
[F] output
OverRange indicator for input 3
UnderR_3
[F] output
UnderRange indicator for input 3
SnsFail_3
[F] output Sensor fail indicator for input 3
NoResponse
[F] output Module not ready indicator
Temperature value:
Signed Integer, represents the measured value according to the selected input range.
Diagnostic flags:
Overrange / Underrange indicators become active when the measurement value is
outside of the specified range for the chosen sensor type.
Sensor fail indicates errors in sensor connection. For RTDs, shorts and opens can be
detected on both, supply lines and sense lines. For thermocouples, the flag indicates
line break.
No Response
:
No response from W745. Check if the module is present on the chosen base ad
-
dress.
FB Status
Parameter structure
:
FB Status
Parameter Type
Description
K 1...16
[K] input
module Number accord. to file D2W745_B.mba
MeasRun
[F] output High when data acquisition is running
DiagRun
[F] output High when sensor diagnostic is running
ComRun
[F] output
High when communication to W745 ok