Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Programming
Programming with PCD Classic
3
3-2
Adjust Window:
Error
Display of communication errors with the module.
Clear button
Button to clear the error.
Initialize module
Shows module initialization progress.
Init button
Button to force manually a check of the module configuration. If
necessary, the module will be reconfigured.
Temperature unit
Selection of temperature unit:
-Celsius:
Temperature values in 1/10°C
-Fahrenheit:
Temperature values in 1/10°F
-Kelvin:
Temperature values in 1/10 K
Channel 0 to 3:
Sensor type
Selection of sensor type.
Configuration / Connection
Selection of input configuration / connection.
Offset
Optional constant temperature offset to correct cabling or sensor
error.
Filter T2
Option to insert a T2 filter. The use of the filter requires 5 supple
-
mentary registers for each channel
Filter time
Time constant (2 times the same value) of the T2 filter.
Diagnose
Diagnose of the channel. Shows Overrange, Underrange, Sensor
failure and Communication error.