Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Programming
Programming with PCD Classic
3
3-1
3
Programming
3.1
Programming with Saia PCD
®
Classic
3.1.1 Programming with Saia PG5
®
FBoxes
For the easy use of the temperature module, an FBox called PCD2.W745 is included
in the standard analogue FBox library of Saia PG5
®
.
First of all, this FBox allows configuring the module according to the individual meas
-
urement setup. Once the FBox has configured the module, it switches automatically
in data acquisition mode. In addition to the reading of the analogue values from the
W745, the FBox delivers powerful diagnostic information about sensor failures.
For correct working, the FBox should be placed in a cyclic organisation block (COB).
FBox name: A name can optionally be given to the FBox.
When several FBoxes are used, FBox must have an individual name.
in0…in3:
Analogue input values (Format / Unit: See chapter 2)
Error:
Channel errors, one byte per input channel:
Error register
Input 3
Input 2
Input 1
Input 0
31 30 29 28
27
26 25 24 23 22 21 20 19 18
17
16 15 14 13 12 11 10 9 8
7
6 5 4 3 2 1 0
x x x x
x x x x
x x x x
x x x x
Comm. error
Comm. error
Comm. error
Comm. error
Sensor error
Sensor error
Sensor error
Sensor error
Underrange
Underrange
Underrange
Underrange
Overrange
Overrange
Overrange
Overrange
Overrange: Measured value is too high for selected range
Underrange: Measured value is too low for selected range
Sensor error: Line break / Open line / No sensor connected
Comm. error: Communication error (no response from module W745)
X:
Not used
Add: Module base address
LED: Green:
Everything ok
Red:
At least one error bit set