Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Appendix
A
A-7
Configuration on PCD3.T760 RIO Module
A.4
Configuration on PCD3.T760 RIO Module
When the PCD3.W745 is used on PCD3.T760 RIO station, 6 registers are available
in the Profi S-IO or Profibus DP configurator.
The 2 first registers (anal_16 , anal_17) contain the diagnostic bits of the 4 inputs
channels.
The first 2 bytes (low bytes) gives the diagnostic bit of 2 analog channels (1 byte per
channel) as indicated in the following screenshot:
Channel 0
Channel 1
Channel 2
Channel 3
Signification of each 8 bits (from right to left) as explained in chapter 3.2.
Bit
Description
0
Over range: The measured value is over the allowed range of the sen
-
sor. The read value in the appropriate PEW (CH0…3) is set to 0xFFFF.
1
Under range: The measured value is under the allowed range of the
sensor. The read value in the appropriate PEW (CH0…3) is set to 0..
2
Reserved (0)
3
Sensor fail: At least one wire connected to this channel is broken. The
read value in the appropriate PEW (CH0…3) is set to the last valid
measured value.
4
Reserved (0)
5
Reserved (0)
6
New value: a new measured value is available. This bit is set to 0 when
reading the status byte.
*)
7
Reserved (0)