X3 Operating Manual
Commissioning
Sartorius
111
4.12.6 Function 8: Diagnosis
Command
Device
address
Function
number
Sub-
function
Any value
CRC 16
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Range 1...127
8
0
This function is intended for testing the communication.
Only sub-function 0 is supported.
The received command is sent as a reply.
Command Device
address
Function
number
Sub-
function
Value of the
command
CRC 16
1 byte
1 byte
2 bytes
2 bytes
2 bytes
4.12.7 Function 15: Writing n Successive Bits
Command Device
address
Function
number
Address of
the 1st bit
Number
of bits
Number of
bytes
Value of
bits
CRC 16
1 byte
1 byte
2 bytes
2 bytes
1 byte
n bytes
2 bytes
Range 0...127
15
0...127
8,16,
24
1,2,3...
/
\
1st byte 2nd byte 3rd byte - - - - - - - - - - -
Last byte
8th ...
1st
bit
last
bit
The bit address must always be the 1st bit of a byte. The number of bits to be read must not be smaller
than 8 and must be a multiple of 8. The address plus the number of bits must not exceed 128.
Example of function 15
Command
1 15 0 64 0 8 1 3
CRC
CRC
Reply
1 15 0 64 0 8 CRC
CRC
The individual bytes are shown.