Cooling
●
Once the compressor stops, it will not start running again for about 3 minutes (*).
(*) Actual compressor OFF time indicated by "3 minutes" varies between 2 minutes 45 seconds to 4 minutes.
●
Thermo. ON : When the room temperature rises above T + 1°F (T°F is set temperature).
Compressor
➞
ON
●
Thermo. OFF : When the room temperature falls below set temperature T°F.
Compressor
➞
OFF
■
Heating (except during defrosting operation)
●
Once the compressor stops, it will not start running again for about 3 minutes (*).
(*) Actual compressor OFF time indicated by "3 minutes" varies between 2 minutes 45 seconds to 4 minutes.
●
Thermo. ON : When the room temperature rises above T°F (T°F is set temperature).
Compressor
➞
ON
●
Thermo. OFF : When the room temperature rises above T + 1°F.
Compressor
➞
OFF
●
Changeover to Heater ON : When the room temperature falls below T – 4°F, the unit turns off heat pump
operation and electric heater comes on instead of compressor.
●
Changeover to Heat Pump : When the room temperature rises above T – 3°F, the unit resumes heat pump
operation and compressor comes on instead of electric heater.