34
■
COOLING
Model Number :
STW0633H2 / 0634H2
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
265V, 1-phase 60Hz
Rating conditions
Running amps.
A
0.09
0.32
1.99
2.4
Power input
kW
0.025
0.085
0.500
0.61
Full load conditions
Running amps.
A
0.09
0.32
2.49
2.9
Power input
kW
0.025
0.085
0.630
0.74
Model Number :
STW0933H2 / 0934H2
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
265V, 1-phase 60Hz
Rating conditions
Running amps.
A
0.09
0.32
2.59
3.0
Power input
kW
0.025
0.085
0.680
0.79
Full load conditions
Running amps.
A
0.09
0.32
3.29
3.7
Power input
kW
0.025
0.085
0.850
0.96
Model Number :
STW1233H2 / 1234H2 / 1235H2
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
265V, 1-phase 60Hz
Rating conditions
Running amps.
A
0.15
0.38
3.67
4.2
Power input
kW
0.040
0.100
0.960
1.10
Full load conditions
Running amps.
A
0.15
0.38
4.77
5.3
Power input
kW
0.040
0.100
1.240
1.38
Model Number :
STW1534H2 /1535H2
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
265V, 1-phase 60Hz
Rating conditions
Running amps.
A
0.15
0.38
5.17
5.7
Power input
kW
0.040
0.100
1.350
1.49
Full load conditions
Running amps.
A
0.15
0.38
6.57
7.1
Power input
kW
0.040
0.100
1.720
1.86
Rating Conditions
: Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 95F (35°C) D.B.
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 115°F (46.1°C) D.B.
Heat pump models (265 V)