5
2-1-4. Heat Pump Type (265 V)
Model Number
Heater class
3.00 kW
STW0633H2
STW0933H2
STW1233H2
4.00 kW
STW0634H2
STW0934H2
STW1234H2
STW1534H2
5.00 kW
STW1235H2
STW1535H2
Voltage (V)
265
Performance
HEAT PUMP
Cooling capacity
BTU/h
7,100
9,000
12,000
14,000
(kW)
(2.08)
(2.64)
(3.52)
(4.1)
Heat pump capaciity
BTU/h
6,400
8,100
10,800
13,300
(kW)
(1.88)
(2.37)
(3.16)
(3.9)
Air Flow....Hi
CFM
315
315
410
410
(CMH)
(535)
(535)
(697)
(697)
Dehumidification
Pints/h
2.3
2.8
3.8
3.8
Electrical Rating
Available voltage range
V
239 to 291
Cooling
Amperes
A
2.4
3.0
4.2
5.7
Watts
W
610
790
1,100
1,490
Power factor
%
96
99
99
99
EER
BTU/hW
11.6
11.4
10.9
9.4
Starting amperes
A
13
15
24
31
Heat pump
Amperes
A
2.2
2.9
3.9
5.2
Watts
W
570
740
1,020
1,350
COP
W/W
3.3
3.2
3.1
2.9
Features
Controls / Temperature control
Mechanical / Themostat
Control unit
Timer
Fan speeds
2
Airflow direction (Indoor)
Horizontal
Manual
Vertical
Air filter
Washable
Air exhaust
Yes
Compressor
Rotary (Hermetic)
R22-Amount charged at shipment
OZ
26.8
30.0
32.1
33.5
Refrigerant control
Capillary Tube
Operation sound
Indoor : Hi / Lo
dB-A
44 / 42
47 / 45
Outdoor
dB-A
60
61
Dimensions & Weight
Unit dimensions
Height
In
15-15/16
(Refer to page 11)
Width
In
41-1/8
Depth
In
21-1/2
Package dimensions
Height
In
18-3/16
Width
In
44-7/8
Depth
In
24-7/8
Weight
Net
lbs
95
100
110
110
Shipping
lbs
110
115
125
125
Shipping volume
Cu Ft
11.7
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Electric Heating Specifications
Electric Heating
Model number
STW0633C2
STW0634C2
STW0933C2
STW0934C2
STW1233C2
STW1234C2
STW1235C2
STW1534C2
STW1535C2
Heater class
kW
3.00
4.00
5.00
Capacity
BTU/h
10,200
13,600
17,000
Electrical rating
Amperes A
11.4
15.2
19.0
Watts W
3,000
4,000
5,000
Recommended circuit protection A
15
20
30