57
10. FUNCTION
10-1. Room Temperature Control
Room temperature control is obtained by cycling the compressor ON and OFF.
■
Cooling
●
Once the compressor stops, it will not start running again for about 3 minutes (*).
(*) Actual compressor OFF time indicated by "3 minutes" varies between 2 minutes 45 seconds to 4 minutes.
●
Thermo. ON : When the room temperature rises above T + 1°F (T°F is set temperature).
Compressor
➞
ON
●
Thermo. OFF : When the room temperature falls below set temperature T°F (T°F is set temperature).
Compressor
➞
OFF
■
Heating
●
Heater ON :
When the room temperature falls below T°F (T°F is set temperature).
Heater
➞
ON
●
Heater OFF :
When the room temperature rises above T + 1°F (T°F is set temperature).
Heater
➞
OFF
Room temp.
T
°
F
T+1
°
F
Heater
ON
ON
OFF
OFF
OFF
OFF
ON
Room temp.
T
°
F
T+1
°
F
Compressor
ON
ON
ON
OFF
OFF
3 minutes
Within
3 minutes
3 minutes
or more
NOTE
Cooling & Electric Heating Models