UPS Characteristics
45
§
1
1
4
4
.
.
4
4
S
S
p
p
e
e
c
c
i
i
f
f
i
i
c
c
a
a
t
t
i
i
o
o
n
n
s
s
Item
Standard or Performance
Notes
Type A11J502A002TU
Model A11J502U002T
Output capacity
5 kVA/4.5 kW
Cooling system
Forced air cooling
Input terminals
Field Wiring Type Terminal block
Number of phases
Single-phase, 2-wire
Voltage
200 V, 208 V, 220 V, 230 V, 240 V
Selectable, rated voltage same as output voltage
At shipment: 200 V *1
Frequency
50 Hz or 60 Hz
Auto-detect, fixed setting selectable,
at shipment: auto-detect *2
Power requirements
5.5 kVA
Max. capacity during battery recovery charging
AC in
pu
t
Input power factor
0.95 or more
During rated input voltage *3
Output terminals
Field Wiring Type Terminal block
Number of phases
Single-phase, 2-wire
Voltage
200 V, 208 V, 220 V, 230 V, 240 V
At shipment: 200 V
Voltage accuracy
Within rated voltage ±2%
Frequency
50 Hz or 60 Hz
Same as input frequency (auto-select)
Frequency accuracy
Within rated accuracy ±1%, 3%, or 5%
1%, 3%, and 5% selectable, at shipment: 3% *4
When UPS free running operation: Within ±0.5%
Voltage waveform
Sine wave
Distortion factor of
voltage waveform
Linear load: 3% or less
When rectifier load: 8% or less
During rated output
Rapid load
change
0%
⇔
100% at transient or output switch
Power outage,
recovery
Within rated voltage ±5 %
During rated output
Transient
voltage
variation Rapid input
voltage change
±10%
variation
Load power factor
0.9 (lag)
Variation range 0.7 (lag) to 1.0
Overcurrent protection
Auto switch to bypass circuit at 110% or more With auto return function *5
Inverter
110% (1 minute) / 118%(instantaneously)
AC o
u
tp
u
t
Overload
capability
Bypass
200% (30 seconds) / 800% (2 cycles)
Type
Small-sized valve regulated lead-acid battery
Quantity
16 (12 V / 1)
Series of 16
Rated capacity
5 Ah / Battery
20 minute-rate
Backup time
5 minutes when load power factor 0.8,
4 minutes when load power factor 0.9
At 25 C (77 F) ambient temperature, initial
value *6
Batte
ri
es
Expected service life
5 years
At 25 C ambient temperature
Generated heat
339 W
During rated output
Input leakage current
4 mA or less
Operating environment
Ambient temperature: 0 to 40°C (32 to 104°F)
Relative humidity: 20 to 90%
No condensation *7
Acoustic noise
45 dB or less
1 m (approx. 40 inches) from front of UPS,
A characteristics
*1. Input voltage range of normal operation will be changed with connected load capacity.
When the load factor is less than 70%, voltage range will be –40% to +15%. When the load factor is 70% or above,
the voltage range will be –20% to +15%.
*2. The allowable range for the input frequency is ±8% when auto-detect is set and 40 Hz to 120 Hz when a fixed setting is
set. When the input frequency recovers from being outside the allowable range, the range is ±8% regardless of which
setting is set. The inverter will not start if the input frequency is not within the range of the values (±1%, ±3, or
±5%) set for the frequency synchronization compliance range.
*3. When the distortion factor of the input voltage waveform is less than 1%.
*4. When the auto-detect setting is set, you can select a frequency compliance range from ±1%, ±3%, and ±5%.
When a fixed frequency is set, the output frequency is fixed to the set frequency (50 Hz or 60 Hz) regardless of the
input frequency.
*5. The inverter is capable of operation synchronized with AC input frequency and switchover operation without
interruption provided that the AC input frequency is within the rated frequency range, and the AC input voltage is
within the rated voltage range.
*6. Some of the specifications for a UPS with long backup times differ from the specifications listed in the table above.
See the extension battery specifications instruction manual.
*7. The UPS contains batteries. The battery service life will be foreshortened if the UPS is used in an environment
where the ambient temperature exceeds 30°C (86°F).