No.
Name
Function
①
PC I/F
PC interface
connector (RS-232C)
Connect the connector and a computer with the supplied communication cable.
This interface functions as follows depending on the setting of “Interface” in the LCD panel
setting menu.
Select the interface according to the function to be used. For the setting procedure, see §3.5
“Setting PC Interface” in
the LCD Panel Operating Manual.
1. Interface setting: WS (work station) (default setting)
Use software such as the power management software on the supplied CD-ROM to
manage the power and shut down the computer by performing communication
between the UPS and computer (personal computer, work station, etc.).
For details on the power management software, see §12 “Using Power Management
Software” or the User’s Guide on the supplied CD-ROM.
2. Interface setting: Standalone
(standalone)
Use the standard UPS service function* of the operating system (NetWare, Windows
NT, etc.) to shut down the UPS automatically.
Signal Names External Appearance
②
CARD I/F
Card interface
connector
Connect the connection cable of an optional Sanyo LAN interface card.
When connecting a LAN interface card, set the interface to WS
(work station). For the
interface setting procedure, see §3.5 “Setting PC Interface” in the
LCD Panel Operating
Manual.
For the LAN interface card installation, see the manual attached in the LAN interface card.
①
②
D-sub 9-pin Male
⑨
⑧
⑦
⑥
⑤
④
③
②
①
Fixing Screw
(inch)
⑤
③
For details on the setting procedure, see
§
13 “Using Standard OS UPS Service.”
When using an operating system (Windows 95 and 98, etc.) that does not have a UPS service
function, do not connect the supplied communication cable. The backup operation may not be
possible in the event of a power outage.
When using a combination of the UPS service function and the power management software
(option) with a serial connection, set the interface to WS
(work station). If the UPS is used
when the setting is set to standalone, the UPS may shut down suddenly when there is a power
* Notes on using the UPS service function
⑥
④
The PC interface connector and
card interface connector cannot be
used at the same time.
Note
2 RXD
3 TXD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
1 DCD
9 RI