![S&P UTBS PRO-REG Series Manual Download Page 7](http://html1.mh-extra.com/html/sandp/utbs-pro-reg-series/utbs-pro-reg-series_manual_3089022007.webp)
7
Example: left side register
Example: left side registe
Model
UTBS PRO-REG
Maximum airflow (m
3
/h)
Motor
Power
(kW)
Frequency
range
(Hz)
Chilled coil/DX
Hot coil
Without coils
2
1300
1500
1500
1x0,55
20-55
3
2500
2500
2500
1x0,75
20-50
5
3800
4500
5100
2x0,75
20-50
8
6500
7400
7500
2x1,1
20-50
Model
UTBS
PRO-REG
Air
flow
(m
3
/h)
Coils Thermal power (kW)
Inlet/Outlet
connections
Hot water coil
Chilled water coil
H2
H4
C4
C6
80ºC/60ºC
50ºC/45ºC
80ºC/60ºC
50ºC/45ºC
7ºC/12ºC
7ºC/12ºC
2
900
11,9
8,3
18,2
22,7
8,1
9,6
1-1/4” GM
1200
14,4
10,0
22,7
15,5
10,0
11,9
3
1700
23,5
16,0
34,7
23,5
15,5
20,0
1-1/4” GM
2500
30,5
20,9
46,8
31,9
20,5
23,3
5
2500
33,9
23,3
51,2
34,7
23,2
29,2
1-1/4” GM
3500
42,7
29,4
66,6
45,2
29,6
38,4
8
4000
55,0
37,7
81,4
55,4
36,0
46,8
1-1/2” GM
6000
72,5
49,8
111,5
76,1
48,2
64,8
* Air inlet temperature: -5ºC, Rel. Hum: 80%.
** Air inlet temperature: 32ºC, Rel. Hum: 50%.
Coil section
Water coils
In the section it can be included one or two water coils (one heating or one cooling coil or
both at the same time). The units can be supplied with 2 or 4 rows for heating coils and 4 or
6-rows for cooling coils. If the unit includes a cooling coil it is always supplied as a standard
with condensate drip tray made for stainless steel AISI 304 and a droplet eliminator. The
connections of the water coil and the drip tray can be ordered on left side or right side of
the unit.
Summary of Contents for UTBS PRO-REG Series
Page 1: ...SERIE UTBS PRO REG EN...
Page 2: ......
Page 29: ...29 10 CONTROL DIAGRAM Version with electric batteries...
Page 30: ...30 Versions with hot and or cold water coils...
Page 31: ...31 Versions with reversible water coil...
Page 62: ...62 22 WIRING DIAGRAMS...
Page 63: ...63...
Page 64: ...64...
Page 65: ...65...
Page 66: ...66...
Page 67: ...67...
Page 68: ...68...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...