Appearance main screen when the unit is confi gured in CAV mode.
CAV control mode selection
Access to the simplifi ed parameter setting menu (via the password 1111) allows:
• The selection of Normal fl ow and Reduced fl ow of each fan.
• The night set point value of the fans.
The choice between normal or reduced fl ow can be performed:
• manually
• automatically by programme schedule (see section Time programming)
• remotely, by external digital contact (see section stop-start remote)
The switch over between the various set points will be done manually or automati-
cally by a time programming.
A third set point, the “night speed”, may be entered via the control panel. The value
in % corresponds to the percentage of the fan’s maximum capacity; it will be used
during the night for free cooling (see corresponding function).
The selection of CAV mode in this installer menu automatically confi gures the screen
of the user menu. The user can then change the unit’s operation without modifying
the settings.
Off: stop the unit.
Manual Reduced fl ow, Manual Normal fl ow: set point manually selection.
Auto: selection of setpoint is done according to time programming.
Summary of Contents for UTBS PRO-REG Series
Page 1: ...SERIE UTBS PRO REG EN...
Page 2: ......
Page 29: ...29 10 CONTROL DIAGRAM Version with electric batteries...
Page 30: ...30 Versions with hot and or cold water coils...
Page 31: ...31 Versions with reversible water coil...
Page 62: ...62 22 WIRING DIAGRAMS...
Page 63: ...63...
Page 64: ...64...
Page 65: ...65...
Page 66: ...66...
Page 67: ...67...
Page 68: ...68...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...