11.4.3. Temperature set point adaptation vs. outdoor temperature
Constant supply air T°C with out-
door T°C compensation
Heating mode
Controller operation is similar to fi rst case. In this
case, main difference is defi ning a compensation
curve defi ned from factory with 8 set points instead
of fi xing a single temperature set point.
Compensation curve
The supply set point is
then adapted with respect
to this curve. At any time,
from the main screen
you can manually change
the supply temperature
(range of +/-3ºC).
11.4.4. Automatic control mode
Depending on the temperatures the controller select the most suitable
temperature control mode, between “Supply temperature control with
compensation for outdoor temperature” and “Room temperature con-
trol”.
11.5. INITIAL TEMPERATURE SETPOINT
To set the setpoint temperature to maintain, keep the following secuence:
Once selected the setpoint temperature.