67
Modbus
Type
Type
Modbus
Address
Bacnet
Address
NA: Not
available
Default
Value
Modbus
Value
Description
Water temp too low, system off
ISR
R
57
BV, 20057
0
0/1
Water temperature below frost
limit value (<7ºC)
Sensor error outdoor temp
ISR
R
59
BV, 20059
0
0/1
Malfunction of outdoor air
temperature sensor
Exchanger frost risk
ISR
R
60
BV, 20060
0
0/1
Exchanger deicing activated
Manual Heater Control
ISR
R
73
BV, 20073
0
0/1
The electric heater is in manual
mode
Manual exchanger control
ISR
R
74
BV, 20074
0
0/1
Heat exchanger in manual control
Internal battery error
ISR
R
80
BV, 20080
0
0/1
Internal battery needs replacing
Sensor error Supply Air temp
ISR
R
90
BV, 20090
0
0/1
Malfunction of supply air
temperature sensor
Sensor error Extract Air temp
ISR
R
91
BV, 20091
0
0/1
Malfunction of extraction air
temperature sensor
Sensor error SAF pressure
ISR
R
96
BV, 20096
0
0/1
Malfunction of supply air
pressure sensor
Sensor error EAF pressure
ISR
R
97
BV, 20097
0
0/1
Malfunction of exhaust air
pressure sensor
Sensor error Exhaust air temp
ISR
R
98
BV, 20098
0
0/1
Malfunction of exhaust air
temperature sensor
Sensor error Frost Protection temp
ISR
R
99
BV, 20099
0
0/1
Malfunction of water
temperature sensor
ETA Filter
ISR
R
131
BV, 20131
0
0/1
Extraction Air Filter needs
replacement
Alarm Acknowledgement
Acknowledgement of individual alarms
HR
R/W
400
NA
To acknowledge an alarm set this signal its alarm
number:
1 = Malfunction of supply air fan
2 = Malfunction of extract air fan
6 = Outdoor Air Filter needs replacement
10 =Fire alarm
11 = Remote On/Off active
23 = Electric Heater Thermal protectors activated
24 = Frost protection function is overriding the control
of the water
25 = Water temperature below frost limit value (<7ºC)
27 = Malfunction of outdoor air temperature sensor
28 = Exchanger deicing activated
41 = The electric heater is in manual mode
42 = Heat exchanger output in manual control
48 = Internal battery needs replacing
49 = Malfunction of supply air temperature sensor
50 = Malfunction of extraction air temperature sensor
55 = Malfunction of supply air pressure sensor
56 = Malfunction of exhaust air pressure sensor
57 = Malfunction of exhaust air temperature sensor
58 = Malfunction of water temperature sensor
90 = Extraction Air Filter needs replacement
Acknowledgement of all alarms
CSR
R/W
3
BV, 10003 Command to acknowledge all activated alarms
INPUTS / OUTPUTS
DI5
ISR
R
18
NA
Value of DI5: Remote normal speed
(Closed: Active Normal speed forced, Open: Normal
speed disabled)
DI6
ISR
R
19
AV, 40019 Value of DI6: Remote ON/OFF
DI8
ISR
R
21
BV, 20021 Value of DI8: Fire alarm (if previously enabled)
DO5
ISR
R
30
BV, 20030 Value of DO5: PWM Electric Heater