30.2. CONFIGURATION OF AN ELECTRICAL PREHEATER
Not necessary in case of SLIM-PH with preheater factory mounted.
Once the preheater installation has been done, it will be necessary to reconfigure the SLIM controller from the SET-
TINGS menu:
31. RESET THE CORRIGO CONTROLLER
In some cases, after several adjustments or due to a bad working, it could be necessary to reset the controller. In such
a case, perform the following sequence of operations:
The ventilation mode of the system (see section "19.1. Commissioning") should now be re-set-up, together with en-
suring that the additional parameters (Language, K-Constant, heater type etc.) are correct. For further details check
section "19. INSTALLER LEVEL".
The same way, all those advanced parameters that were configured before the reset was performed, must be reconfigu-
red after the reset (Night free-cooling, time settings, Modbus/Bacnet communication, fire alarm strategy).
32. INTEGRATION IN BUILDING MANAGEMENTS SYSTEMS (BMS)
32.1. CONNECTION TO BMS - MODBUS
32.1.1. MODBUS RTU on port 2 - RS 485
Controller number 1 (see section "14.2.1. External electrical box -
composition") has a RS485 communication port (P2) that can be dedi-
cated to Modbus RTU communication.