S&C Instruction Sheet 1072-530
39
SpeedNet Client Tool
Interfaces Window,
Serial Mode Tab
Figure 65. The Serial Mode interface configuration window.
The following serial port modes are available: See Figure 65.
• PPP
—The Point-to-Point Protocol (PPP) mode is used for emulating an Ethernet
connection over a serial interface. This is currently used for communication with a
SpeedNet Radio in an IntelliRupter fault interrupter through the fault interrupter’s
Wi-Fi interface. SpeedNet Radios do not route traffi c to other radios from the PPP
interface due to security concerns
• DNP
—The Distributed Network Protocol (DNP) mode is used for transferring DNP
data between the SpeedNet Radio serial port and other Ethernet devices
• Repeater/SpeedGate
—The Repeater/SpeedGate mode is used for SpeedNet Radios
that operate as fi xed repeaters within a network
• Serial Pass-Through
—The Serial Pass-Through feature allows support for legacy
equipment on the serial port using non-DNP3 serial protocols, such as Modbus
• Apply
—Saves changes made to the
Serial Mode
window. Changes will not be saved
if you select a different confi guration tab without fi rst clicking the
Apply
button
PPP Serial Mode
The following options are available when PPP is the selected serial port mode, as shown
in Figure 65.
• Local IP Address
—IP address (Ethernet Interface) assigned to the SpeedNet Radio’s
end of the PPP link
• Remote IP Address
—IP address assigned to the remote device of the PPP link
Figure 66. PPP Protocol settings.