4 S&C Instruction Sheet 766-557
Overview
These instructions cover the procedure for operating the IntelliRupter PulseCloser Fault
Interrupter Docking Station. This device powers the protection and control module
when it is removed from the IntelliRupter fault interrupter, and permits uploading and
downloading configuration settings, by using a dedicated base memory module. The
docking station can also be used with a communication module when it is removed from
the IntelliRupter fault interrupter and installed in the docking station with a protection
and control module. The protection and control module provides the power for the com-
munication module and permits programming the radio, verifying radio operation, and
charging the communication module battery.
The docking station may be used to monitor serial communication traffic between
the protection and control module and the communication module, using either a secure
Wi-Fi connection to your personal computer or a direct connection to your serial-port-
equipped personal computer. A user-furnished DNP test set, such as manufactured by
ASE, may be connected to the docking station to monitor DNP messages.
The docking station includes a Wi-Fi radio antenna. Connectors are provided for a
user-furnished SCADA radio antenna and a user-furnished GPS receiver antenna.
The docking station may be powered from 88 to 264 V, 50/60 Hz. It is intended for
indoor use only.
NOTICE
To ensure that previously programmed settings in the protection and control module
are not lost when the module is installed in the docking station, you must unplug the
base memory module from the docking station .
If the base memory module is not
unplugged from the docking station when the docking station is powered up,
the protection and control module will upload the most recently applied settings
stored in the base memory module.