S&C Instruction Sheet 766-557 15
Step 3
When DU connection status changes from
Trying connection on 127.0.0.1
to
Not con-
nected
, select the
Communications Setup
tab at the top center of the window. The new
tab window is shown in Figure 13.
Figure 13. Download Utility (DU) file location.
Step 4
Your settings may not exactly match Figure 13, but the important parameters are shown
there. Set the
Conn. Type
to
Serial
and that the correct
Comm Port
is selected. The
Baud
Rate
should be set to
57600
.
Do not change the
DNP Settings
: the
Peer Addr
, or
Our Addr
settings. Use the settings
configured in Download Utility.
Step 5
When you have set all parameters on the
Control Software Loader
Communication Setup
tab, click the
Connect
button.
Step 6
When status indicates that
Download Utility
is connected, navigate to the
Download/
Upload
tab and click the
Start Download
button. When prompts appear asking whether
or not to
Skip a Download
, you should click the
No
button.
Step 7
When download is complete, do not exit
Download Utility
. Navigate back to the
Com-
munication Setup
tab and change the
Conn. Type
back to
UDP/IP
. Then click the
Exit
button to close the Download Utility.
Serial Connection—Rev. 3.4.x and Earlier