11
▶ Resistance Temperature
Detector(RTD) Input
▶ DC Voltage input
▶ DC Current input
(3) Electric power circuit
(4) Measurement (Sensor) input circuit
● Use the cable with equivalent or above the vinyl insulated cable (KSC3340) or
electric cable for electric power circuit.
● Make the circuit for ground with the electric cable over 2mm and above the
third class ground (Unver100Ω of ground resistance)
● Make 1 point ground from the ground terminal and the wiring cross the ground
terminal shall not be made.
● Switch off the electric power to SDR100E main body and external power supply when the measurement (Sensor) input circuit
is made because of the electric shock risk.
● Use the cable with shield for the input circuit. In addition, make 1 point ground for the shield.
● Make the circuit off from the electric power circuit or ground circuit for the signal line for measuring input.
● Use the electric cable with small cable resistance and no difference in resistance among 3 cables.
'(
_7"$
The 3rd
class ground
SHIELD
RTD
R
+
-
+
-
1
2
3
A
b+
B-
The 3rd
class ground
SHIELD
1
2
3
A
b+
B-
V
The 3rd
class ground
SHIELD
1
2
3
A
b+
B-
mA
01. Cautions (Instructions) for safety
Summary of Contents for SDR100E Series
Page 23: ...Main screen Part 03...
Page 25: ...4 1 Graph recording screen 24 Graph recording setting Part 04...
Page 36: ...5 1 Graph view 35 5 2 Data searching 36 Graph searching Part 05...
Page 39: ...Function setting Part 06...
Page 51: ...Part 08 Setting canned message...
Page 53: ...Setting reserve operation Part 09...
Page 64: ...Part 11 Error history display...
Page 68: ...Part 12 Setting system parameter...
Page 70: ...13 1 Sensor input screen 69 Screen for setting the sensor input Part 13...
Page 95: ...DI function and operation Part 16...
Page 102: ...System initial setting9 Part 18...