Locating the Units (Continued)
Install the outdoor unit higher than 150mm from the base surface and install
the drain hole to connect the pipe to the drainage.
If forward fan outdoor unit is installed where has average fallen snow 150mm
over, outward duct should be attached to the outdoor unit.
The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
When heating, condensed water may be generated. Pay attention to
waterproof and drainage of the concrete foundation where the outdoor unit is
installed. (An ice road may form on the base surface in winter)
Make up for wire mash or steel bar so that the outdoor unit is not damaged or
broken when installing concrete foundation.
When installing the outdoor units in same place simultaneously, install the H
beam inside concrete foundation. (When installing a number of outdoor unit,
you can install it on the concrete foundation)
Install the H beam(150mm x 150mm x t10 : basic specification) to jut out from
the concrete foundation.
After installing the H beam, apply corrosion protection.
Install a square pad(t=20mm or more) to prevent vibration of the outdoor unit
delivering to the base surface when installing the concrete for the outdoor unit.
Place the outdoor unit on the H beam and fix it with the bolt, nut and washer.
Installing the Outdoor Unit
Do not install the outdoor unit on a wood palette.
Fix the outdoor unit completely to the base surface with anchor bolts.
The manufacturer is not responsible for the damage occurred by not
keeping standard of the installation.
CAUTION
< When installing on the ground >
Drain hole
150 or more
< When installing on the roof >
Install the outdoor unit
horizontally on
the ground
150 or more
Base mount construction
Outdoor unit
Anchor bolt
Nut, Spring
washer
H beam
Square pad
A+10~20mm or more
A
20mm
75mm
(Unit : mm)
RVXMHF04E0A_E_IM_24820.indd 10
2006-02-01 ¿ÀÈÄ 5:02:23