Electrical Connections (Continued)
You should connect the power cable into the power cable terminal and fasten it with a
clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly it may shorten the life of the condenser.
If the unbalanced power is exceeded over 4% of supply rating, the indoor unit is
protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power cable
and the connection cord of the indoor and outdoor units in the iron pipe.
Connect the power cable to the auxiliary circuit breaker. An all pole disconnection
from the power supply must be incorporated in the fixed wiring(≥3mm).
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and communication cable.
Power cable should be used within maximum length limitation.
Each indoor unit power should be supplied between maximum and minimum values.
The power cable is not supplied with the air conditioner.
For the power cable, use the grade H07RN-F or H05RN-F materials.
Outdoor unit
Model
(Series)
Power Supply
3 Phase
1 Phase
Power
Supply(V)
Max/
Min(V)
MCCB/
ELB
Power
cable
Max
Length
Power
Supply(V)
Max/
Min(V)
MCCB/
ELB
Power
cable
Max
Length
RVXMHF040E
RVXMHF050E
-
-
-
-
-
220-
240V~/
50Hz
242/198
30A
5.5 mm
2
18m
RVXMHF050G
380-
415V~/
50Hz
418/342
16A
2.0mm
2
18m
220-
240V~/
50Hz
242/198
16A
2.0 mm
2
18m
RVXMHF060G
20A
3.5mm
2
18m
20A
Specification of electronic wire of the outdoor unit
Power Supply (1 Phase)
Earth Cable
Communication
cable
Power Supply Max/Min(V)
Power cable
Max length
220-240V~/50Hz
242/198
2.0mm
2
Decided by power drop
among indoor units
2.0~5.5mm
2
0.75~1.25mm
2
Specification of electronic wire of the indoor unit
coef: Use approximately 1.55
L
k
: Distance between each unit[m], A
k
: Thickness of power cable[mm
2
]
i
k
: Running current of each unit[A]
∑ (
Coef
×35.6×L
k
×i
k
) <20[V]
1000
×A
k
n
k=1
Select the thickness and length of power cable for total drop of electric pressure to be less than
10%(On 220V lnput voltage basis).