Locating the Units (Continued)
Outdoor unit base mount and anchor bolt position
When tightening the anchor bolt
Tighten the rubber washer to prevent the outdoor unit bolt connection
part from corroding.
CAUTION
Rubber washer
(Unit : mm)
Anchor bolt position
(ø7, 4 holes )
When installing 1 outdoor unit
Outdoor unit
(Rear side)
More than
1/50 slope
Open to air
Drain
plug
When installing more than 1 outdoor unit
Outdoor unit
(Rear side)
More than 1/50 slope
Open to air
Drain
plug
Outdoor unit
(Rear side)
Outdoor unit
(Rear side)
Open the upside of connected parts of outdoor units to prevent inner pressure.
Do not place a trap on the concentrated pipe. And install the drain pipe
horizontally with a slope of 1/50 or more.
Insulate the drain pipe and drain plug by using the insulation over 10t.
Install a self-regulation heat cable to prevent the drain pipe from freezing.
Installing the drain pipe