IPM (inverter) overheating
If you don’t use heat paste or don’t tighten the screws into the heat sink you will see
E500.
Tighten the screws, put heat paste under the chip s and check the fan motor top runs
when the compressor is running
E554
Gas leak error. The unit has detected that there is no rise in compressor discharge
temperature despite the compressor operating, this means there is a refrigerant
error.
Carry out test on page 6.