E251, Temperature Sensors
E251
is an error with the compressor discharge pipe sensor. It’s
the blue sensor on the pipe leaving the compressor. It’s
connected to the main PCB in connector at the top right of the
PCB called CN43 in a white and red plug; it’s the 3
rd
and 4
th
wire
from the top.
To read what this sensor is
measuring you can ask the unit
using the interrogation function
on the outdoor unit main PCB
At the bottom of the main PCB
are 4 buttons, you need to press
K4 5 times.
The display will show 05 XX, the XX will be the temperature this
sensor is measuring; this sensor measures the compressor gas
temperature you will need to compare the pipe temperature with
the reading, if they are different the sensor needs replacing.
Note:
If this temperature is very high (over 80C) it
usually indicates there are refrigerant
problems, you will need to do a capacity test
in HW mode.