51
English
Fiel
d S
etting Mode
࡙
4012 : The temperature of forced heating priority (Refer to 4011)
࡙
4013 : If the ambient temperature > 4013, Heating Mode stops in auto mode.
࡙
Code 50**
ࣕ
User’s options for extra functions
501*: New target temperatures of each mode (Heating/Cooling/DHW) when “Outing” function is on
࡙
5011: Value of cooling leaving water temperature setting when “Outing” function is on
࡙
5012: Value of cooling indoor’s room temperature setting when”Outing” function is on
࡙
5013: Value of heating leaving water temperature setting when “Outing” function is on
࡙
5014: Value of heating indoor’s room temperature setting when”Outing” function is on
࡙
5017: Value of Water Law’s floor control (#2041=1) leaving water temperature setting when “Outing”
function is on
࡙ ߦߡߢߩࡠǤɇ̷Їʪͱ˙Ǯɇϩʪθøɇи࣭ϑAƸʀͱ͝ϩθͱ̷࣍ࢄߣߡߥߢॉߣ̷࣎ʪɇӬ͝˝иɇϩʪθϩʪ͔ΧʪθɇϩЇθʪϑʪϩϩ̈͝˝и˵ʪࣨ͝ĮЇϩ̈͝˝ࣩ
function is on
࡙
5019: Value of DHW tank’s temperature setting
5021: Offset temperature setting when Economic DHW operation is on (During Economic DHW
operation, temperature will be automatically set lower by value of #5021(°C) than actual setting)
504*: Smart Grid control
࡙
5041: Application of Smart Grid control
࡙
5042: Heater application during Smart Grid control
ࣕ
0: Heater off during Smart Grid control
ࣕ
1: Heater control during Smart Grid control
ࣕ
2: Not use
࡙
5043: Input Voltage from Smart Grid contact port
ࣕ
0: If Smart Grid Voltage = 0V, Smart Grid Control is Operated
ࣕ
1: If Smart Grid Voltage = 5V, Smart Grid Control is Operated
࡙
5061: Water supply capacity ratio compared to heating: The load of hot water tank if designed
heating (floor or Fan coil unit) load is 7
ex) When required heating load is 14000W, required hot water tank load 10000W, 10000/14000x7= Set 5