24
English
Fiel
d S
etting Mode
Air to Water Heat Pump: Only AE*** Model
CAUTION
࡙
Set the FSV value of the product other than the specified models by referring to the FSV label provided
with the manual of the product, and then attach it on the control box's cover. The FSV values in the table
are applied to the specified models.
NOTE
࡙
Be sure to reset the power when changing the FSV (#3041 to 3046) of disinfection operation and the
FSV (#5011 to 5019) of setting the outing mode.
Field Setting Value (FSV) 10**
Code 10** : Upper and lower temperature limits of each operation mode of wired remote controller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
࡙
The values in the following table are just examples for your understanding.
Main Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)
RNW***
MODEL CODE :
MIM-E03CN
Setting Standard
Setting Standard
Item
Step Unit
Default Min. Max. Default Min. Max.
Remote
Controller
Setting
Range Code
10**
Cooling
Water Out Temperature for
Cooling
Max
1
ঐ
1011
25
ߢߩ
25
25
ߢߩ
25
Min
1
ঐ
1012
16
5
ߢߩ
16
5
ߢߩ
Room Temperature for
Cooling
Max
1
ঐ
1021
30
ߣߩ
30
30
ߣߩ
30
Min
1
ঐ
1022
ߢߩ
ߢߩ
ߣߩ
ߢߩ
ߢߩ
ߣߩ
Heating
Water Out Temperature for
Heating
Max
1
ঐ
1031
65
37
65
65
37
65
Min
1
ঐ
1032
25
15
37
25
15
37
Room Temperature for
Heating
Max
1
ঐ
1041
30
ߢߩ
30
30
ߢߩ
30
Min
1
ঐ
1042
16
16
ߢߩ
16
16
ߢߩ
DHW
DHW tank Temperature
Max
1
ঐ
1051
55
50
70
55
50
70
Min
1
ঐ
1052
40
30
40
40
30
40
NOTE
࡙
The FSV #3011 in the wired remote controller should be set to 1 or 2 to use the DHW mode.
Field setting mode