2-12
Samsung Electronics
Product Specifications
Functional Development Specifications
(cont.)
Installation/Service Modes
(cont.)
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
4
1
Indoor unit main address checking
1,2
-
Main address (0~63)
-
Indoor unit main address setting (outdoor unit reset is needed to set)
3,4
-
Main address (0~63)
-
Indoor unit RMC address setting/checking
5,6
-
RMC address (00H~2FH)
-
2
Indoor unit option code setting/checking
1)*
-
Indoor unit option code (24 bits)
-
3
Indoor unit option switch setting/checking
1)*
-
Refer to the indoor unit installation
manual for details
-
5
1
AHU setting/checking
Setting/checking the
differential value
1,2
-
0~30
1
RPM setting/checking
3,4
-
0~25
1 RPM
filter performance
5
-
0 – Pre
1 – Medium performance
2 –High performance
-
humidity setting/checking
6
-
0 – 30, 1 - 40, 2 - 50
-
2
AHU discharge temperature setting/
checking
Use of discharge
temperature control
1
-
0 – No use, 1 - Use
-
Cooling discharge temperature
3,4
-
10 ~25°C
1°C
Heating discharge temperature
5,6
-
28 ~43°C
1°C
3
Fresh Duct discharge temperature
checking
Cooling discharge temperature
1,2
-
13~25
1°C
Heating discharge temperature
3,4
-
18~30
1°C
6
1
ERV Plus setting/checking
Use of cold air prevention
1
-
0 – No use, 1 - Use
-
Use of humidification when Heating
thermo off
2
-
0 – No use, 1 - Use
-
Use of fan operation in Defrost
3
-
0 – No use, 1 - Use
-
Use of humidification when Heating
4
-
0 – No use, 1 - Use
-
2
ERV Plus temperature
setting/checking
Cooling
1,2
-
15~30°C
1°C
Heating
3,4
-
15~30°C
1°C
3
ERV Plus Auto mode temperature setting/
checking
Set temperature
1,2
-
15~30°C
1°C
Set temperature difference
3,4
-
5~15°C
1°C
4
Setting/checking the compensating temperature A under the Heating
EEV control for ERV Plus
1,2
-
0~10°C
1°C
Checking the compensating temperature B under the Heating
EEV control for ERV Plus
3,4
-
0 – Non use of humidifier(0°C)
1 – Use humidifier(10°C)
-
5
ERV Plus fan RPM setting/checking
Air supply RPM
1,2
-
10~27 RPM
1 RPM
Air exhaustion RPM
3,4
-
10~27 RPM
1 RPM
0
Factory setting
1
-
0 – No use, 1– Factory setting
-
1)* Data1 is the option setting page. / Data2~6 stand for the option codes.
You can set the 24 digits options.
Page
Option Settings
How to Move Between Pages
Page
Option Settings
How to Move Between Pages
PAGE 1
1
st
~5
th
digit option setting
Press the [>] button to go to PAGE 2.
PAGE 4
16
th
~20
th
digit option setting
Press the [>] button to go to PAGE 5.
PAGE 2
6
th
~10
th
digit option setting
Press the [>] button to go to PAGE 3.
PAGE 5
21
th
~24
th
digit option setting
-
PAGE 3
11
th
~15
th
digit option setting
Press the [>] button to go to PAGE 4.
1 2 3 4 5 6
Option Code
Option Setting Page
Regardless of Celsius and Fahrenheit setting, service mode setting is available only with Celsius.
Maximum no. of Connections: A maximum of 16 "indoor units + ERV" can be connected.
Separate control between indoor unit and ventilation system (ERV) is possible.
Integrated control between indoor unit and ventilation system (ERV) is possible.
유선리모컨_MWR-WE10_E_33320A(1)_1.indd 12
2010-12-23 오후 5:51:16
Summary of Contents for MWR-WE10
Page 20: ...MEMO Samsung Electronics 2 17 ...