Samsung Electronics
2-11
Product Specifications
Functional Development Specifications
(cont.)
Installation/Service Modes
(cont.)
●
If your indoor machine does not support the setting mode, then you may not be able to edit the settings or apply your changes.
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
1
1
Wireless remote controller Option
setting/checking (1)
Cooling/Heating selection
1
0
0 – Cooling/Heating,
1 – Cooling only
-
Use of wireless remote controller
2
1
0 – No use, 0 - Use
-
MAIN/SUB wired remote controller
3
0
0 –MAIN, 1- SUB
-
Temperature unit
4
0
0 – Celcius(°C), 1 – Fahrenheit(°F)
-
2
Wireless remote controller Option
setting/checking (2)
Temperature sensor selection
1
0
0 – Indoor unit,
1 – Wired remote controller
-
Use of average temperature
2
0
0 – No use, 0 - Use
-
Use of Auto mode
3
1
0 – No use, 0 - Use
-
Temperature display
4
0
0 – Set temperature,
1 - Room temperature
-
AC On/Off button function
5
0
0 – Indoor unit + ERV,
1 – Indoor unit only,
2 – ERV only,
-
3
Blade
setting/checking
Lock of Blade1
1
0
0 – Unlock, 1 – lock
-
Lock of Blade2
2
0
0 – Unlock, 1 – lock
-
Lock of Blade3
3
0
0 – Unlock, 1 – lock
-
Lock of Blade4
4
0
0 – Unlock, 1 – lock
-
4
ERV option
Setting/checking
Use of By-Pass mode
1
0
0 – No use, 1 - Use
-
Use of Auto mode
2
0
0 – No use, 1 - Use
-
Use of air purification mode
3
0
0 – No use, 1 - Use
-
Use of external control
4
0
0 – No use, 1 - Use
-
5
Room Temperature compensation
Temperature control reference
1,2,3
0
-9 ~ 40(°C)
0.1(°C)
Temperature compensation value
4,5,6
0
-9.9 ~ 9.9(°C)
0.1(°C)
6
Number of connected units
Number of indoor units
1,2
-
0 ~ 16
-
Number of ERVs
3,4
-
0 ~ 16
-
7
Temperature increment/decrement (°C only)
1
0
0-1°C, 1-0.5°C, 2-0.1°C
-
0
Factory option setting
1
0
0 – Unchanged
1 – Factory setting
-
2
1
Software code
1~6
-
Software code
-
2
Software version
1~6
-
Software version
-
3
1
Indoor unit room temperature
1,2,3
-
Room temperature
°C
2
Indoor unit EVA IN temperature
1,2,3
-
EVA IN temperature
°C
3
Indoor unit EVA OUT temperature
1,2,3
-
EVA OUT temperature
°C
4
Indoor unit EEV step
1,2,3
-
EEV step
-
5
Indoor unit option checking (1)
Use of central control
1
-
0 – No use, 1 - Use
-
Use of drain pump
2
-
0 – No use, 1 - Use
-
Use of electric heater
3
-
0 – No use, 1 - Use
-
Use of hot water coil
4
-
0 – No use, 1 - Use
-
6
Indoor unit option checking (2)
Use of external control
1
-
0 – No use, 1 - Use
-
Use of RPM compensation
2
-
0 – No use, 1 - Use
-
Filter time
3
-
0 – 2000 hours, 1 – 1000 hours
-
Heating temperature compensation
4
-
0-2°C, 1-5°C
-
EEV stop step in heating
5
-
0 – 1/80 steps, 1 – 80
-
유선리모컨_MWR-WE10_E_33320A(1)_1.indd 11
2010-12-23 오후 5:51:15