5. Parameters
5-9
5.2 Terminal status LED
When command is input to a terminal, corresponding LED is turned on.
#6 #1
Control relay output status
Power relay output status
Brake action status
None (Not used)
DC-braking on start
DC-braking on stop
Contact input status
Contact output status
5-10
MOSCON-E7 User’s Manual
5.3 B-Parameter
The B-parameters are used in order to change the basic settings related
to the operation modes of the inverter, capacity of the inverter & the
motor, and to control the initialization.
5.3.1 Basic setup
5.3.1.1 Selecting the source of frequency command : B0.01
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during operation
B0.01
Active source
of frequency
command
- 00~23 00
X
Digit1
Digit0
B0.01
Active source of frequency
command in local mode (0~2)
Active source of frequency
command in remote mode (0~3)
• B0.01 is used to select the source of the frequency command.
• Active source of frequency command in local and remote mode can be
selected independently. Normally, unless the local mode is selected,
the source of frequency command in remote mode is the active one.
• Setting
Setting
constant
Source of command frequency
0 Operator
(Digital
volume)
1 Operator
(Keypad)
2
Analog frequency command (Voltage or current: terminal 9 or 10)
3 Communion
(RS-485)
5.3.1.2 Selecting the source of RUN command : B0.02
Parameter
No.
Name
Unit
Setting
range
Factory
Setting
Changeable
during operation
B0.02
Active source
of RUN
command
- 00~12
00
X
• B0.02 is used to select the source of the run command.