Troubleshooting
8-3-4 When the fan of indoor unit does not operate
1. Checklist :
1) Is the power voltage normal?
2) Is the connector of indoor fan with the good contact? (CN72)
3) Is the soldering status of running condenser (CR71) with the good contact?
4) Is connector of the Hall IC with the good contact (CN44)?
5) Is the indoor fan rotating when it is under operation mode?
2. Troubleshooting procedure
Put the power off and put it on after 5 seconds.
Replace the indoor unit PCB Ass'y due to the
Micom defect.
Replacement of indoor unit
fan motor.
Is the operation icon(
) lamp
flickering with the sound of "ting"?
Is the type of MICOM (IC04)
pin #48 old type ?
120Hz
Error(Error Code : E3)
occurs after the indoor
unit fan motor is rotating
for 15 seconds?
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Is the pin #15 of IC07(ULN2003A)
the old type?
Is the pin #17 of MICOM the
old type?
120Hz
If the power is not available (indoor unit),
refer to page 96.
Replace of indoor unit PCB Ass'y.
Replace the IC07(ULN2003A) and
SS71(G3MB202PL or AQG22212)
Replace Q501(2SC2412K)
If the operation/stop button of the remote
control is pressed, is the operation lamp(
) and
then is the indoor fan rotating after 5~6 seconds?
Is AC 120V and higher shown across the indoor fan
connector (CN72) ?
DB98_20402A(1)_2 10/26/04 3:27 PM Page 97
Summary of Contents for MH052FDEA
Page 106: ...MEMO 105 Samsung Electronics ...
Page 113: ...Samsung Electronics 112 Exploded Views and Parts List 1 2 8 9 10 11 3 6 7 4 5 ...
Page 132: ...131 Samsung Electronics 11 PCB Diagram 11 1 MAIN PCB Indoor Unit TOP ...
Page 133: ...Samsung Electronics 132 PCB Diagram BOTTOM ...
Page 136: ...135 Samsung Electronics 11 2 MAIN PCB Outdoor Unit 11 2 1 MH068FXEA4 MH080FXEA4 TOP ...