Operation Instruction & Installation
25
Samsung Electronics
Concrete
Suspension bolt(M8)-field supply
Hole in anchor
Hole in plug
Insert
Shipping
block
Ceiling support
Rubber
Drain hose port
When the drain hose is installed to the right.
3mm
■
MH052FDEA
It is recommended to install the refnet joint before installing the indoor unit.
1. Carefully remove the indoor unit from the packing case and pull out the shipping
block on the motor of the unit.
2. Place the pattern sheet on the ceiling at the spot where you want to install the indoor
unit.
Note
: Since the diagram is made of paper, it may shrink or stretch slightly due to temperature
or humidity. For this reason, before drilling the holes maintain the correct dimensions
between the markings; refer to page 6.
3. Insert bolt anchors. Use existing ceiling supports or construct a suitable support as
shown in figure.
4. Install the suspension bolts depending on the ceiling type.
IMPORTANT:
• Ensure that the ceiling is strong enough to support the weight of the
indoor unit.
Before hanging the unit, test the strength of each attached suspension bolt.
IMPORTANT:
• If the length of suspension bolt is more than 1.5m, it is required to prevent
vibration.
5. Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
IMPORTANT:
• You must install the suspension bolts more than four when installing the indoor
unit.
6. Hang the indoor unit to the suspension bolts between two nuts.
Note
: Piping must be laid and connected inside the ceiling when suspending the unit.
If the
ceiling is already constructed, lay the piping into position for connection to the unit before
placing the unit inside the ceiling.
7. Screw the nuts to suspend the unit.
8. Adjust level of the unit by using measurement plate for all 4 sides.
Note
: For proper drainage of condensate, give a 3mm slant to the left or right side of the unit
which will be connected with the drain hose, as shown in the figure. Make a tilt when you
wish to install the drain pump, too.
DB98_20402A(1)_1 10/26/04 2:48 PM Page 25
Summary of Contents for MH052FDEA
Page 106: ...MEMO 105 Samsung Electronics ...
Page 113: ...Samsung Electronics 112 Exploded Views and Parts List 1 2 8 9 10 11 3 6 7 4 5 ...
Page 132: ...131 Samsung Electronics 11 PCB Diagram 11 1 MAIN PCB Indoor Unit TOP ...
Page 133: ...Samsung Electronics 132 PCB Diagram BOTTOM ...
Page 136: ...135 Samsung Electronics 11 2 MAIN PCB Outdoor Unit 11 2 1 MH068FXEA4 MH080FXEA4 TOP ...