Feature & Operation
81
Samsung Electronics
6-1-10 Defrost control
Defrost operation is controlled by sensing the temperature of indoor heat exchanger.
◆
How to sense defrost conditions
A condition
The temperature of indoor heat exchanger is checked in intervals of 1 minute. In case the temperature of indoor heat exchanger drops more
than 0.5°C for 6 minutes, it is considered as one cycle. If it happens 3 times continuously, It is said that "A condition" is satisfied.
B condition
If the temperature of indoor heat exchanger is below about 40±3°C when the compressor is on, it is considered as defrost "B condition"
C condition
When the accumulating time of compressor ON is over 20 minutes.
D condition
When the accumulating time of compressor ON is over 3Hr.
E condition
When operating time of compressor without stopping is over 6 minutes.
F condition
If the compressor is off(thermo off) when the temperature of indoor heat exchanger is below about 46°C, it is considered as one cycle.
If it happens 2 times continuously, It is said that "F condition" is satisfied.
G condition
When the accumulating time of compressor ON is over 90 minutes.
◆
Defrost operation conditions
AXBXC
condition or
BXDXE
condition
FXG
condition
Defrost time : 5~8 minutes
◆
Operation pattern
Defrost
Compressor
Outdoor Fan
4-Way Valve
Indoor Fan
ON
ON
ON
ON
55sec
1min
Defrost Time
OFF
OFF
OFF
ON
ON
more than 58sec
2sec
55sec
1min
Low Speed
Thermo ON
Setting Speed
OFF
OFF
ON
DB98_20402A(1)_1 10/26/04 4:09 PM Page 81
Summary of Contents for MH052FDEA
Page 106: ...MEMO 105 Samsung Electronics ...
Page 113: ...Samsung Electronics 112 Exploded Views and Parts List 1 2 8 9 10 11 3 6 7 4 5 ...
Page 132: ...131 Samsung Electronics 11 PCB Diagram 11 1 MAIN PCB Indoor Unit TOP ...
Page 133: ...Samsung Electronics 132 PCB Diagram BOTTOM ...
Page 136: ...135 Samsung Electronics 11 2 MAIN PCB Outdoor Unit 11 2 1 MH068FXEA4 MH080FXEA4 TOP ...