Message Description
message, with no special change in
the sequence.
The warning message disappears on
reversion to the normal state.
E006
BATT CONNECTION
WARNING
When the battery connection is
abnormal.
This is the connection warning
message, with no special change in
the sequence.
The warning message disappears on
reversion to the normal state.
[Table 7-2: Inverter general events warning list]
7.2.2
INVERTER General Events (Protection)
Type
Code
Description
Measures
PROTECTION
E101
GRID RMS OVER
CURRENT PROTECTION
The product stops the generating
process because a significant
PROTECTION event has occurred.
Wait until the event message
disappears. After the event message
is removed, it automatically returns
to normal.
If it is not removed until the time
limit is reached, it is converted to a
significant event.
E102
DC LINK OVER VOLTAGE
PROTECTION
The product stops the generating
process because a significant
PROTECTION event has occurred.
Wait until the event message
disappears. After the event message
is removed, it automatically returns
to normal.
If it is not removed until the time
limit is reached, it is converted to a
significant event.
E103
PV STRING1 REVERSE
CONNECTION
PROTECTION
The product stops the generating
process because a significant
PROTECTION event has occurred.
Wait until the event message
disappears. After the event message
is removed, it automatically returns
to normal.
If it is not removed until the time
limit is reached, it is converted to a
significant event.
E104
PV STRING2 REVERSE
The product stops the generating