82
SAMSUNG ELECTRONICS
9-2-10 Compressor starting error
Indoor display
7 SEG DISPLAY
DESCRIPTION
C461
Comp starting error
Outdoor display
Comp starting error
: LAMP ON
: LAMP OFF
: LAMP BLINK
1. Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power
.
Is the restart error occurred again?
Is the connection of compressor wire is normal?
NO
YES
NO
YES
Terminate the service
Connectthecomp wire normally
Download the EEPROM data
Is the restart error occurred again?
Is the compressor body and interphase
resistance insulated?
NO
YES
NO
YES
Terminate the service
Exchange the Outdoor PBA
Exchange the compressor