Product Specifications
Samsung Electronics
2-17
Indoor Unit(cont.)
Q
Ceiling type
Model
AM056FNCDEH/TK
AM071FNCDEH/TK
Power Supply
ø/V/Hz
1/220~240/50
1/220~240/50
Mode*
1)
HP / HR
HP / HR
Performance
Capacity
Cooling*
2)
kW
5.6
7.1
Btu/h
19,100
24,200
Heating*
3)
kW
6.3
8.0
Btu/h
21,400
27,200
Condensate (with High fan speed)
Liters/h
2.87
2.87
Power
Input
W
72/72
80/77
Running Current
A
0.33/0.28
0.35/0.29
Sound Level
Sound Pressure (Cooling / Heating)*
4)
dB(A)
45/45
47/47
Fan
Type
-
Sirocco Fan
Sirocco Fan
Motor
Model
-
Y5S413B214
Y5S413B214
Type
-
Non Feedback SSR
Non Feedback SSR
Output
W
*5)
*5)
Airflow Rate
Cooling (High)
m
3
/min
16.5
16.5
Heating (High)
m
3
/min
20.0
20.0
Refrigerant
Type
-
R410A
R410A
Control Method
-
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
6.35
9.52
Gas (Flare)
ø, mm
12.7
15.88
Drain
ø, mm
VP25 (OD 32,ID 25)
VP25 (OD 32,ID 25)
Weight
Net Weight
kg
21.0
21.0
Shipping Weight
kg
25.5
25.5
Dimensions
Net Dimensions (W x H x D)
mm
1000x650x200
1000x650x200
Shipping Dimensions (W x H x D)
mm
1080x730x300
1080x730x300
Functions
Auto Restart
-
O
O
Auto Swing
-
X
X
Group/Individual Control
-
O
O
External Contact Control
-
O
O
Trouble Shooting by LED
-
X
X
Standard
Accessories
Installation Manual
-
O
O
Operation Manual
-
O
O
Pattern Sheet for Installation
-
X
X
Flexible Drain Hose
-
O
O
Filter / Safety Grille
-
Filter (Washable)
Filter (Washable)
Optional
Accessories
Wireless Remote Controller
-
AR-DH00
AR-DH00
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
*1)
Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB , Equivalent refrigerant piping : 7.5m , Level differences : 0m
*3) Norminal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB , Equivalent refrigerant piping : 7.5m , Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.