2-26
Samsung Electronics
Indoor Unit(cont.)
Q
GD-S(Big Duct)
Model
AM180JNHPKH/TK
AM224JNHPKH/TK
Power Supply
ø/V/Hz
1/220-240/50
1/220-240/50
Mode*
1)
HP / HR
HP / HR
Performance
Capacity
Cooling*
2)
kW
18.0
22.4
Btu/h
61,400
76,400
Heating*
3)
kW
20.0
25.0
Btu/h
54,300
67,600
Condensate (with High fan speed)
Liters/h
-
-
Power
Input
W
340
530
Running Current
A
1.9
2.9
Sound Level
Sound Pressure (High/Low)*
4)
dB(A)
42
44
Fan
Type
-
Sirocco Fan
Sirocco Fan
Motor
Model
-
DL-17860SSBA
DL-17860SSBA
Type
-
BLDC
BLDC
Output
W
Airflow Rate
High/Mid/Low
m
3
/min
58/50/43
72/61/50
External Static Pressure
Standard(Min.~Max)
mmH
2
O
7.34(5-20)
7.34(5-20)
Refrigerant
Type
-
R410A
R410A
Control Method
-
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
9.52
9.52
Gas (Flare)
ø, mm
19.05
19.05
Drain
ø, mm
VP25(OD25, ID20)
VP25(OD25, ID20)
Weight
Net Weight
kg
82.5
82.5
Shipping Weight
kg
92
92
Dimensions
Net Dimensions (W x H x D)
mm
1350 x 910 x 450
1350 x 910 x 450
Shipping Dimensions (W x H x D)
mm
1612 x 984 x 519
1612 x 984 x 519
Functions
Auto Restart
-
O
O
Auto Swing
-
X
X
Group/Individual Control
-
O
O
External Contact Control
-
O
O
Trouble Shooting by LED
-
X
X
Standard
Accessories
Installation Manual
-
O
O
Operation Manual
-
O
O
Pattern Sheet for Installation
-
O
O
Flexible Drain Hose
-
O
O
Filter / Safety Grille
-
X
X
Optional
Accessories
Wireless Remote Controller
-
MR-DH00
MR-DH00
Duct Receiver
Kits
Receiver
-
MRK-A10
MRK-A10
Receiver Wire
-
MRW-10A
MRW-10A
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
Drain Pump
-
MDP-G075SQ
(Internal installation)
MDP-G075SQ
(Internal installation)
MDP-G075SP
(External installation)
MDP-G075SP
(External installation)
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.