![Samsung 136S Installation Manual Download Page 142](http://html.mh-extra.com/html/samsung/136s/136s_installation-manual_21064142.webp)
3
.
Installing the Product
Confidential
124
English 8/2019. Rev 0.0
Figure 3-152: System BMS Install Setting Window
Important
Change the values according to your system configuration.
[Count] Rack per 1 System: Number of racks connected to the same System BMS
[Count] Module per 1 Rack: Number of modules for each rack (e.g., 136S1P Rack has 17
modules)
[TCPIP] items (IP Address, Subnet Mask, Gateway, Port)
TCP/IP address and port (17.91.30.246/502 by default), subnet mask (255.255.224.0 by default)
and gateway (17.91.1.2 by default) should be changed according to your network environment.
Set the port number to the factory default values
(Port#01: 502, Port#02: 602, Port#03: 702)
[RTU] items: set to the factory default values.
(Baud rate: 0, Parity: 1, Slave ID: 0x27)
[Operation] Neutral Control Enable
Set to “0” if all racks are connected in parallel (default).
Set to “1” if the two racks are connected in series for a three-wire connection.
[Operation] Customer ID
Set according to the dry contact input and output options. Refer to 2.1.3 SMPS Assembly (Type
A / Type B)
Summary of Contents for 136S
Page 1: ...Confidential English 8 2019 Rev 0 0 LIB System for UPS Installation Manual 136S ...
Page 4: ...Confidential English 8 2019 Rev 0 0 ...
Page 10: ...Important Safety Instructions Confidential vi English 8 2019 Rev 0 0 ...
Page 18: ...Confidential Table of Contents viii English 8 2019 Rev 0 0 ...
Page 153: ...Confidential Memo ...
Page 154: ...Confidential Memo ...
Page 155: ...Confidential Memo ...
Page 156: ...www SamsungSDI com ...