8-14
EB 6495-2 EN
Operation
with holding register 55 (Controller [1]) and
115 (Controller [2])
u
− Value 1 = Set point SP1 active
− Value 2 = Set point SP2 active
− Value 3 = Set point SP3 active
− Value 4 = Set point SP4 active
The switchover over Modbus has the same
priority as switchover using the keys.
The set point switchover cannot be per-
formed either using the keys or over Modbus
if the set point switchover over the digital in-
puts is configured.
8.4 Locking the controller
The controller can be protected against un-
authorized access. There are three ways to
implement the locking of the controller:
−
Locking the operating level
Î
See section 8.4.1.
−
Locking all keys over a digital input
Î
See section 8.4.2.
−
Activating key number operation
Î
See section 8.4.3.
8.4.1 Locking the operating
level
Switchover between manual and automatic
mode as well as changes to the set point for
both Controller [1] and Controller [2] can be
locked independently from one another.
Locking is performed in the
C.7 Operator
keys
submenu of either Controller [1] or [2]
by setting the configuration items
C.7.2-1
Lock manual/auto key
= On and/or
C.7.3-1 Lock set point keys
= On.
Example:
The set point adjustment of Con-
troller [1] is to be locked.
The controller is currently in the operating
level.
Î
Enter the configuration menu (see the
'Start-up and configuration' section).
Summary of Contents for TROVIS 6495-2
Page 6: ...EB 6495 2 EN...
Page 46: ...6 6 EB 6495 2 EN...
Page 90: ...8 26 EB 6495 2 EN...
Page 94: ...9 4 EB 6495 2 EN...
Page 96: ...10 2 EB 6495 2 EN...
Page 98: ...11 2 EB 6495 2 EN...
Page 100: ...12 2 EB 6495 2 EN...
Page 102: ...13 2 EB 6495 2 EN...
Page 104: ...14 2 EB 6495 2...
Page 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Page 108: ...15 4 EB 6495 2 Certificates...
Page 109: ...EB 6495 2 15 5 Certificates...
Page 110: ...15 6 EB 6495 2...
Page 185: ......