16-26
EB 6495-2 EN
Annex A (configuration guide)
Con-
troller
C.3.1
Control response
Default
setting
Setting
[1]
[2]
[1] [2]
KP
Proportional-action coefficient
[0.01 ... 100.0]
1.00
[1] [2]
TN
Reset time <C.3.1.1-1/-4/-5>
[1 ... 9999 s]
120 s
[1] [2]
TV
Derivative-action time
<C.3.1.1-3/-4>
[1 ... 9999 s]
10 s
[1] [2]
Y0
Operating point
[–10.0 ... 110.0 %]
0.0 %
[1] [2]
TV.K
Derivative-action gain
<C.3.1.1-3/-4>
[0.00 ... 10.00]
1.00
C.3.1.2
Limit I-component
<C.3.1.1-1/-4/-5>
C.3.1.2-0
[1] [2]
-0
Off
[1] [2]
-1
On
[1] [2]
I.MIN
Minimum I-component
<C.3.1.2-1>
[–120.0 ... 0.0 %] –100.0 %
[1] [2]
I.MAX
Maximum I-component
<C.3.1.2-1>
[0.0 ... 120.0 %] 100.0 %
C.3.1.3
Error
C.3.1.3-1
[1] [2]
-1
Not inverted
[1] [2]
-2
Inverted
[1] [2]
-3
Inverted via DI1
[1] [2]
-4
Inverted via DI2
[1] [2]
-5
Inverted via DI3
[1] [2]
-6
Inverted via DI4
[1] [2]
E.TZ
Dead band
[0.00 ... 110.00 %]
Firmware version 1.11 and lower
[0.0 ... 110.0 %]
[1] [2]
E.MIN
Min. effective error signal
[–110.0 ... 110.0 %]
[1] [2]
E.MAX
Max. effective error signal
[–110.0 ... 110.0 %]
C.3.1.4
Assign D-component
<C.3.1.1-3/-4>
C.3.1.4-1
[1] [2]
-1
To error signal
[1] [2]
-2
To controlled variable
C.3.1.5
Control mode changeover P(D)/PI(D)
<C.3.1.1-1/-4>
C.3.1.5-0
[1] [2]
-0
Off
[1] [2]
-1
With digital input DI1
[1] [2]
-2
With digital input DI2
[1] [2]
-3
With digital input DI3
[1] [2]
-4
With digital input DI4
[1] [2]
-5
By error
[1] [2]
E.SMIN
Min. limit for PI(D) behavior
<C.3.1.5-5>
[–999.0 ... 999.0 %]
–10.0 %
Summary of Contents for TROVIS 6495-2
Page 6: ...EB 6495 2 EN...
Page 46: ...6 6 EB 6495 2 EN...
Page 90: ...8 26 EB 6495 2 EN...
Page 94: ...9 4 EB 6495 2 EN...
Page 96: ...10 2 EB 6495 2 EN...
Page 98: ...11 2 EB 6495 2 EN...
Page 100: ...12 2 EB 6495 2 EN...
Page 102: ...13 2 EB 6495 2 EN...
Page 104: ...14 2 EB 6495 2...
Page 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Page 108: ...15 4 EB 6495 2 Certificates...
Page 109: ...EB 6495 2 15 5 Certificates...
Page 110: ...15 6 EB 6495 2...
Page 185: ......