EB 6495-2 EN
7-7
Start-up and configuration
Return to the operating level
…
Return to the operating level stepwise.
7.1.2.1
Configuration
example
Based on a default setting (1x Fixed set
point/follow-up control
M.1-1
), the analog
input AI1 is to be set to Pt 1000. The mea
-
suring range is to be 0 to 200 °C.
The following requirements are met:
−
The code of the configuration item to de
-
termine the input signal is
I.1.1
, see
configuration list (see Annex A).
−
Lower and upper range values are set in
the
AI1.MIN
and
AI1.MAX
parame-
ters. Both parameters are assigned to the
I.1.1
configuration item.
−
The following position in the configura
-
tion menu can be found using the code
of the configuration item:
–
I
Menu
I Input
–
I.1
1 Analog input AI1
sub-
menu
–
I.1.1
1 Input signal
configura
-
tion item
The analog input AI1 can only be configured
as a Pt 1000 input when the DIP switches
are positioned for “Pt 100/Pt 1000“.
Both DIP switches AI1 (at the side of the
controller housing) must set to the position
“Pt 100/Pt 1000“ (see the 'Operation'
section).
The controller is currently in the operating
level:
Î
Enter the configuration menu (see sec
-
Configure the input signal
1x
Select
I Input
menu.
1x
Enter
I Input
menu.
The
I.1 Analog input AI1
submenu
is highlighted.
Note
Summary of Contents for TROVIS 6495-2
Page 6: ...EB 6495 2 EN...
Page 46: ...6 6 EB 6495 2 EN...
Page 90: ...8 26 EB 6495 2 EN...
Page 94: ...9 4 EB 6495 2 EN...
Page 96: ...10 2 EB 6495 2 EN...
Page 98: ...11 2 EB 6495 2 EN...
Page 100: ...12 2 EB 6495 2 EN...
Page 102: ...13 2 EB 6495 2 EN...
Page 104: ...14 2 EB 6495 2...
Page 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Page 108: ...15 4 EB 6495 2 Certificates...
Page 109: ...EB 6495 2 15 5 Certificates...
Page 110: ...15 6 EB 6495 2...
Page 185: ......