7-10
EB 6493 EN
Start-up and configuration at the device
or
..............
and
, followed
by
Parameter selec
-
tion
Parameter name
Value range
1)
See
KP
Proportional-action coefficient
[0.1 …
1.0
… 100.0]
u
TN
Reset time
[1 …
120
… 9999 s]
TV
Derivative-action time
[1 …
10
… 9999 s]
TVK1
Derivative-action gain
[0.10 …
1.00
… 10.00]
Y.PRE
Operating point
[–10.0 …
0.0
… +110.0]
DZXD
Dead band error Xd
[
0.0
… 110.0 %]
DZXD
Minimum effective error Xd
[
–110.0 %
…
DZXD]
DZXD
Maximum effective error Xd
[
DZXD …
110.0 %
]
1)
Default setting is in
bold
print.
The controller is in the operating level.
The reading on the display looks like this.
Î
Open configuration level.
Reading:
PAR
(Control parameters menu)
Î
3 x
Select CNTR (Controller) menu.